Lenze · Decentralised frequency inverter 8400 motec (EtherNet/IP™ option) · EDS84DMOTEIP EN 2.0 - 10/2013

30

Commissioning

Setting the IP configuration of the Inverter Drive 8400 motec

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

6.3

Setting the IP configuration of the Inverter Drive 8400 motec

The IP configuration is required for addressing the Inverter Drive 8400 motec to ensure that

communication between the PC/»Engineer« or the scanner and the drive can be effected via

EtherNet/IP. For this, an IP address, subnet mask, and gateway address must be allocated. You have

the following options to select the IP parameters for the Inverter Drive 8400 motec:

Setting via the EtherNet/IP configurator of the »Engineer«

( 31)

Setting via codes in the »Engineer«

( 33)

Setting via a BOOTP/DHCP server

( 35)

Setting via the TCP/IP Interface Object (0xF5)

( 35)

Note!

• The assignment of invalid combinations of IP address, subnet mask, and gateway

address can have the consequence that no connection to the EtherNet/IP network can

be established.

• Codes

C13010

(IP address),

C13011

(subnet mask),

C13012

(gateway address), and

C13016

(multicast IP address) show the IP parameters currently used.

• In the case of impermissible settings, the error message

EtherNet/IP: Invalid IP

Parameters [0x01bc6533]

( 84)

is output.