I/O data transfer (implicit messages)

I/O configuration with »RSLogix 5000« version 20 or higher

69

Lenze · Decentralised frequency inverter 8400 motec (EtherNet/IP™ option) · EDS84DMOTEIP EN 2.0 - 10/2013

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

12. Create an "alias tag".

Example with the assembly object instance 23 (0x17):
For a forward motion of a conveyor, bit ’0’ (Run Fwd) is to be referenced by byte ’0’.

Right-click an assembly tag and select the command "New Tag..." in the context menu.

Instance

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

23

(0x17)

0

Net

Ref

NetCtrl

Fault

Reset

Run

Rev

Run

Fwd

1
2

Speed Reference (Low Byte)

3

Speed Reference (High Byte)

4

Torque Reference (Low Byte)

5

Torque Reference (High Byte)

Note!

NetCtrl (Bit 5) and NetRef (Bit 6) have to be set in order that the drive can receive

start/stop commands and speed/torque command via the network.

• In order to be able to use the torque control of the assembly object distance 23 (0x17),

the "DriveMode" attribute has to be written by means of explicit message

transmission.

Write "DriveMode" attribute

( 138)