34

Commissioning

Setting the IP configuration of the Inverter Drive 8400 motec

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

IP address
The IP address is set/changed in

C13000

.

The IP address currently used is displayed in

C13010/1...4

.

Subnet mask
The subnet mask indicates which part of the IP address is evaluated as net ID or host ID.
Valid subnet masks are defined in accordance with RFC 1878
The subnet mask is set/changed in

C13001

.

The subnet mask currently used is displayed in

C13011/1...4

.

Gateway address
The gateway address is valid if the network address of the IP address and the gateway address are

identical.
If the gateway address and the IP address are identical or if the address is ’0.0.0.0’, gateway

functionality is not used.
The gateway address is set/changed in

C13002

.

The gateway address currently used is displayed in

C13012/1...4

.

Example: Display of the IP address 192.168.124.16
Code

C13010/1

C13010/2

C13010/3

C13010/4

Value

192

168

124

16

Example: Display of the subnet mask 255.255.255.0
Code

C13011/1

C13011/2

C13011/3

C13011/4

Value

255

255

255

0

Example: Display of the gateway address 192.168.124.16
Code

C13012/1

C13012/2

C13012/3

C13012/4

Value

192

168

124

16