1 write parameters, Write parameters, Parameter data transfer (explicit messages) – Lenze E84DGFCG User Manual

Page 74

Advertising
background image

Lenze · Decentralised frequency inverter 8400 motec (EtherNet/IP™ option) · EDS84DMOTEIP EN 2.0 - 10/2013

74

Parameter data transfer (explicit messages)

Write parameters

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

9.1

Write parameters

In order to write data into code C00011 (reference speed) of the Inverter Drive 8400 motec by

means of explicit message transfer, for example, the following settings are necessary:

Settings

Value / description

Message Type

"CIP Generic"

Service Type

"Set Attribute Single" (service code "0x10")

Class

"6E" (access to Lenze code)

Instance

"11" = Lenze code C00011 of Inverter Drive 8400 motec

Attribute

"1" = Subcode of the Lenze code

• If the corresponding Lenze code does not have a subcode, the value ’1’

must be entered here.

• A display code cannot be configured by the "SET" service.

Source Element

Variable in the PLC program used as data source for writing.

Source Length

The source length has to be set to the length (data type) of the current

parameter (see parameter reference in the software manual/online help of

the drive).

For writing to code C00011, set the source length to "2 bytes".