Lenze · Decentralised frequency inverter 8400 motec (EtherNet/IP™ option) · EDS84DMOTEIP EN 2.0 - 10/2013

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

8.2

I/O data mapping

I/O data transfer takes place via the MCI interface.

• The I/O data are accessed via the port blocks MCI_IN and MCI_OUT. These port blocks are also

referred to as I/O data channels.

• The MCI_IN port block maps the received data objects.
• The MCI_OUT port block maps the data objects to be sent.
• To the scanner, up to 10 data words (max. 20 bytes) can be sent.
• From the scanner, up to 8 data words (max. 16 bytes) can be received.
• The ports/function blocks of the I/O data objects are interconnected with the Lenze »Engineer«.

[8-1]

Outer and inner data transfer between bus system, inverter, and application

Field bus

8400

Application

Communication Unit

Drive Unit

MCI_IN

Word 1

...

Word 8

MCI_OUT

Word 1

...

Word 10

Software manual / online help for the Inverter Drive 8400 motec
Here you will find detailed information on the port/function block interconnection in

the »Engineer« and on the port blocks.