Internal switch latency

The integrated 2-port switch causes runtime delays. For "store-and-forward" and 100 Mbps, these

runtime delays can be calculated as follows.
Runtime delay for an output data packet of the scanners incl. 32-bit "run/idle header" with 16-bit

sequence counter:

Runtime delay for an output data packet of an adapter without 32/bit "run/idle header":

Example
Delay of an output data packet of the scanners with 8 output data words (16 bytes):

• ((66 permanent bytes + 16 bytes) x 8 x 10 nsec) + 4 μsec
• (82 bytes x 8 x 10 nsec) + 4 μsec
• 6.56 μsec + 4 μsec = 10.56 μsec

Runtime delay = ((66 permanent bytes + I/O data in bytes) x 8 x 10 nsec) + 4 μsec

Runtime delay = ((62 permanent bytes + I/O data in bytes) x 8 x 10 nsec) + 4 μsec

Note!

The use of external switches can also lead to runtime delays. Depending on the system

constellation, it may be useful to create a star topology or a line/mix topology.

Network topology

( 22)