Lenze · Decentralised frequency inverter 8400 motec (EtherNet/IP™ option) · EDS84DMOTEIP EN 2.0 - 10/2013

52

I/O data transfer (implicit messages)

I/O configuration in the »Engineer«

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

8.5

I/O configuration in the »Engineer«

8.5.1

Lenze technology application / configuring user-definable parameter sets

How to configure the Lenze technology applications / user-definable parameter sets in the

»Engineer«:

1. Select the application (C00005 = 1000) in the Application parameters tab.

In the example, the "speed actuating drive" application is configured.

2. Make the default setting of the I/O configuration.

Select "MCI" control mode (C00007 = 40).