Monitoring

Fault with regard to EtherNet/IP communication
The response of the Inverter Drive 8400 motec to a fault with regard to EtherNet/IP communication

can be set in the »Engineer« under the Monitoring tab.

Settings

Description

Idle Mode

The 32-bit real time header sent by the scanner is evaluated.

• Run/idle flag (bit 0) = 1:

• The scanner indicates the validity of the I/O data.

• Run/idle flag (bit 0) = 0:

• The I/O data are invalid and the response parameterised here (

C13880/

1

) is executed on the drive.

• The I/O data are processed as set in

(

C13885

).

Overall Ethernet

Communication Timeout

If after the time set in

(

C13881

) there is no longer any access via the

»Engineer«, the response parameterised here is activated in the drive

(

C13880/4

).

Fault Mode

The adapter (Communication Unit) monitors the I/O connection to the

scanner.

If no "implicit message" has been received within the timeout time for

implicit messages parameterised by the scanner, the response

parameterised here (

C13880/2

) is executed on the drive.

Overall Ethernet Timeout Time Here, the overall message timeout time (

C13881

) is set.

If no message has been received within this time, the response

parameterised in

(

C13880/4

) is executed.

The following messages are monitored:

• Implicit messages

• Explicit messages

• »Engineer« access via EtherNet/IP

Explicit Msg Timeout

If no "explicit message" has been received within the timeout time for

explicit messages parameterised by the scanner, the response

parameterised here (

C13880/3

) is executed on the drive.

Clear I/O Data

(

C13885

), serves to set the I/O data to be processed by the adapter to

maintain internal communication if ...

• the CIP network status (

C13862

) of the controlling I/O connection is not

"Connected" or

• an idle event has occurred.