I/O data transfer (implicit messages)

I/O configuration with »RSLogix 5000« version 20 or higher

65

Lenze · Decentralised frequency inverter 8400 motec (EtherNet/IP™ option) · EDS84DMOTEIP EN 2.0 - 10/2013

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

8. Go to the "Module Definition" dialog window and make the connection settings.

The terms "input" and "output" refer to the point of view of the scanner:

• Assembly input objects (input) are sent from the adapter to the scanner.
• Assembly output objects (output) are sent from the scanner to the adapter.


Settings for Lenze technology applications or user-definable parameter sets:

Select "Exclusive Owner - Custom" connection.

If you use the Lenze technology applications or user-definable parameter sets in the

drive, the "Exclusive Owner - Custom" assembly object instance always has to be

selected.

Set Data type = INT.

The INT data type is exchanged via the ports MCI_IN and MCI_OUT of the Inverter Drives

8400. In case of the SINT data type, an additional PLC logic is required for conversion.

Set Tag Suffix = 1.

A tag suffix formulates a module-describing tag name.