Commissioning

6.3

Setting the IP configuration of the Inverter Drive 8400 protec

28

Lenze · Decentralised frequency inverter 8400 protec (EtherNet/IP™ option) · Communication Manual · DMS 3.0 EN · 07/2014 · TD17

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

6.3

Setting the IP configuration of the Inverter Drive 8400 protec

IP configuration is necessary in order to assign an address to the Inverter Drive 8400 protec so that

communication between the PC/»Engineer« or the scanner and the inverter is possible via

EtherNet/IP. For this purpose, an IP address, subnet mask and gateway address have to be assigned.

You can assign these IP parameters for the Inverter Drive 8400 protec in the following ways:

Setting via the EtherNet/IP configurator of the »Engineer«

( 29)

Setting via codes in the »Engineer«

( 31)

Setting via a BOOTP/DHCP server

( 33)

Setting via the TCP/IP Interface Object (0xF5)

( 33)

Note!

• The assignment of invalid combinations of IP address, subnet mask, and gateway

address can have the consequence that no connection to the EtherNet/IP network can

be established.

• Codes

C13010

(IP address),

C13011

(subnet mask),

C13012

(gateway address), and

C13016

(multicast IP address) show the IP parameters currently used.

• In the case of impermissible settings, the error message

EtherNet/IP: Invalid IP

Parameter [0x01bc6533]

( 80)

is output.