Parameter data transfer (explicit messages)

9.2

Read parameters

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

9.2

Read parameters

In order to read out Lenze code C00011 of the Inverter Drive 8400 protec by means of explicit

message transfer, for example, the following settings are necessary:

Settings

Value / description

Message Type

"CIP Generic"

Service Type

"Get Attribute Single" (service code "0x0E")

Class

"0x6E" (access to Lenze code)

Instance

"11" = Lenze code C00011 of Inverter Drive 8400 protec

Attribute

"1" = Subcode of the Lenze code

If the corresponding Lenze code does not have a subcode, the value ’1’ must

be entered here.

Destination

Variable in the PLC program the drive data will be copied to.

When reading code C00011, make sure that the tag used as destination is a

single word in UINT16 format.