I/O data transfer (implicit messages)

8.5

I/O configuration with »RSLogix 5000« version 19 or lower

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

7. Under I/O Configuration in the configuration tree, right click "1769-L32E Ethernet Port

LocalENB" and select "Properties".

8. Go to the Connection tab and set further properties.

Required setting

Optional settings

9. Complete the settings with OK.

• The I/O configuration is now complete.
• The corresponding tags will then be created in the "Controller Tags" of the controller

project.

10. The last step is

Saving the I/O configuration in »RSLogix 5000«

( 68)

.

Setting

Description

Requested Packet

Interval (RPI)

Set RPI 4.0 ms. (Standard setting: 10 ms)

The RPI [ms] specifies the intervals for the I/O data exchange between the inverter

(adapter) and the controller (scanner).

Settings

Description

Inhibit module

This option serves to interrupt or inhibit the communication to the adapter.

Major Fault On

Controller If Connection

Fails While In Run Mode

This option serves to put the drive into the error status if the EtherNet/IP connection

to the inverter fails while the controller is running.

Use Unicast Connection

over EtherNet/IP

Option deactivated (standard setting):

• The input data is sent from the adapter to the scanner by means of multicast

telegrams.

• Other scanners can access this data in addition to the currently configured

scanner ("Listen only" or "Input only" connections).

Option activated:

The input data is sent from the adapter to the scanner by means of unicast

telegrams.