11 diagnostics – Lenze E84Dxxxx User Manual

Page 76

Advertising
background image

11

Diagnostics

11.1

LED status displays

76

Lenze · Decentralised frequency inverter 8400 protec (EtherNet/IP™ option) · Communication Manual · DMS 3.0 EN · 07/2014 · TD17

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

NS

Green

Red

Off

Off

CIP network status: "No IP Address"

The device is not supplied with voltage or does not yet have an IP

address.

Off

On

CIP network status: "Duplicate IP"

The device has no access to the fieldbus (IP address conflict).

Off

Blinking

CIP network status: "Connection Timeout"

A time-out is executed.

On

Off

CIP network status: "Connected"

The device is working correctly and has established a connection to the

scanner.

Blinking

Off

CIP network status: "No Connections"

The device ...

• is working correctly;

• has been assigned an IP address;

• has not been integrated into the network by the scanner yet.

Blinking

Blinking

CIP network status: "Self-Test"

The device is in the state of self testing.

Err

Red

On

A communication error has occurred.

Lnk/Act1

Lnk/Act2

Yellow

On or

flickers

Data are exchanged via Ethernet.

LED

Colour / Status

Description

250 ms

250 ms

250 ms

250 ms

250 ms

250 ms

50 ms