Lenze · Decentralised frequency inverter 8400 protec (EtherNet/IP™ option) · Communication Manual · DMS 3.0 EN · 07/2014 · TD17

31

6

Commissioning

6.3

Setting the IP configuration of the Inverter Drive 8400 protec

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

6.3.2

Setting via codes in the »Engineer«

You can also set the IP parameters manually in the »Engineer« under the Settings tab. The values

will be transferred to the corresponding codes.

How to activate changed settings in the »Engineer«:

1. Execute device command C00002 = "11: Save all parameter sets".

The current IP configuration is stored in the memory module of the inverter.

2. Carry out a "type 0 reset" to the

Identity Object (1 / 0x01)

( 108)

of the bus node or 8400

switch the voltage supply of the Inverter Drive 8400 protec off and then on again.

Settings

Description

IP Config Control

Selection (

C13005

) of how the IP configuration is to be made:

0: The IP configuration currently stored in the Inverter Drive 8400 protec

is used.

1: The IP configuration is assigned by a BOOTP server using the BOOTP.

2: The IP configuration is assigned by a DHCP server using the DHCP.

IP Address

Setting of the IP address (

C13000

)

Subnet Mask

Setting of the subnet mask (

C13001

)

Gateway Address

Setting of the gateway address (

C13002

)

Multicast IP Start Address

Setting of the Multicast IP start address (

C13006

)

Setting the multicast configuration ( 34)

Multicast Config TTL Value

Setting of the multicast TTL value (

C13019

)