Lenze · Decentralised frequency inverter 8400 protec (EtherNet/IP™ option) · Communication Manual · DMS 3.0 EN · 07/2014 · TD17

81

12

Error messages

12.2

Possible causes and remedies

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

EtherNet/IP: Fault Mode [0x01bc8111]

EtherNet/IP: Explicit Message Timeout [0x01bc8112]

EtherNet/IP: Overall Ethernet Timeout [0x01bc8114]

EtherNet/IP: Ethernet cable pulled out [0x01bc8121]

EtherNet/IP: Idle Mode [0x01bc8132]

Response (Lenze setting printed in bold)

Setting:

C13880/2

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

• Connection to scanner has been interrupted.

• Controlling I/O connection failed by timeout.

• Within the timeout time for implicit messages

parameterised by the scanner, no "implicit messages"

have been received.

• Check cables and terminals.

• Plug in the network cable into the Ethernet port.

• Check Requested Package Interval (RPI) of I/O

connection.

• Increase timeout time for implicit messages.

Response (Lenze setting printed in bold)

Setting:

C13880/3

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

• Connection to scanner has been interrupted.

• Failure of an explicit connection

• Within the timeout time for explicit messages

parameterised by the scanner, no "explicit messages"

have been received.

• Check cables and terminals.

• Plug in the network cable into the Ethernet port.

• Check Requested Package Interval (RPI) of the explicit

connection.

• Increase timeout time for explicit messages.

Response (Lenze setting printed in bold)

Setting:

C13880/4

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

• Failure of »Engineer« communication via Ethernet

• When the time set in

C13881

has expired, there is no

access via the »Engineer«.

• Check cables and terminals.

• Plug in the network cable into the Ethernet port.

• Increase the overall Ethernet timeout time in

C13881

.

Fault with regard to EtherNet/IP communication

( 73)

Response (Lenze setting printed in bold)

Setting: not possible

None  system fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

• Network cable has been detached from the Ethernet

terminal.

• Network cable (plug) is defective.

• Plug the network cable into the Ethernet terminal.

• Check the network cable (plug) and replace it if

necessary.

Response (Lenze setting printed in bold)

Setting:

C13880/1

None  system fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

• Scanner has received an idle event.

• The scanner is in the "PROG" mode.

• In the "Scanner Command Register", the run/

idle flag (bit 0) is 0.

Set the scanner to the run mode.

Run/idle flag (bit 0) = 1