1 write parameters, Write parameters, 9parameter data transfer (explicit messages) – Lenze E84Dxxxx User Manual

Page 70

Advertising
background image

9

Parameter data transfer (explicit messages)

9.1

Write parameters

70

Lenze · Decentralised frequency inverter 8400 protec (EtherNet/IP™ option) · Communication Manual · DMS 3.0 EN · 07/2014 · TD17

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

9.1

Write parameters

In order to write data into code C00011 of the Inverter Drive 8400 protec by means of explicit

message transfer, for example, the following settings are necessary:

Settings

Value / description

Message Type

"CIP Generic"

Service Type

"Set Attribute Single" (service code "0x10")

Class

"0x6E" (access to Lenze code)

Instance

"11" = Lenze code C00011 of Inverter Drive 8400 protec

Attribute

"1" = Subcode of the Lenze code

• If the corresponding Lenze code does not have a subcode, the value ’1’

must be entered here.

• A display code cannot be configured by the "SET" service.

Source Element

Variable in the PLC program used as data source for writing.

Source Length

For writing to code C00011, set the source length to "2 bytes".