Lenze · Decentralised frequency inverter 8400 protec (EtherNet/IP™ option) · Communication Manual · DMS 3.0 EN · 07/2014 · TD17

53

8

I/O data transfer (implicit messages)

8.5

I/O configuration with »RSLogix 5000« version 19 or lower

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

8.5

I/O configuration with »RSLogix 5000« version 19 or lower

The following example describes the I/O configuration of the Allen-Bradley 1769-L32E

CompactLogix controller using the Rockwell »RSLogix 5000« programming software up to version

19.
Up to and including software version 19 the I/O configuration is carried out without

EDS files

( 25)

.

How to carry out the I/O configuration, taking the CompactLogix controller 1769-L32E

with »RSLogix 5000« as an example:

1. Click the I/O Configuration folder in the configuration tree.

For the 1769-L32E CompactLogix controller, the I/O configuration already includes a local

Ethernet port.
If a SoftLogic or ControlLogix controller is used, an Ethernet port scanner needs to be added

to the configuration.