7overload, 1 overload protection of the frequency monitoring), 2 overload protection of the motor – Lenze 8615E User Manual

Page 101

Advertising
background image

7

Overload

7.1

Overload protection of the frequency

monitoring)

The frequency

have an output current monitoring to

them against overload. You

adapt this protection to the

maximum ambient temperature to be expected. The lower the

max.

ambient temperature, the

the limit of the permissible

continuous output current. The permissible continuous output
powes rises the same way.

Cl 19 and Cl20 you

enter

three settings:

l

Rated power up to a maximum of 50°C

l

Increased power up to a maximum of 45°C

l

Maximum power up to a maximum of 40°C

be activated

when using the units 8605, 8607, 8611, 8615)

the output current exceeds the set limit, a fault is indicated after

30 to 60 seconds (see page 148).

7.2

Overload protection of the motor

For motor protection, you

use the

PTC input

terminals 11, 12).

You

use the input to connect a PTC thermistor or a thermal

contact. The motor monitoring is already activated by connecting

the monitoring circuit of the motor to terminals 11 and 12 (remove
wire bridge).

If the motor is overheated, you

the monitoring of the

PTC input such that

l

no

is released

l

TRIP is activated, see page 148

l

a warning is indicated, see page 150

Select the TRIP set-input by

Cl 19 =

and

the

via

(see page 82).

Code

Name

Parameter (Factoty setting printed in

bold)

Acceptance

Digital input

TRIP-Set

SH + PRG

Monitoring

PTC

input

Output power monitoring)