5.3

Operation with DC-bus supply

5.3.1 Connection of several drives

Drives

are supplied by a three-phase voltage

also be

linked via the terminals +UG and -UG for energy-sharing. This type
of connection requires all

to be supplied simultaneously

with the same mains voltage, with

being connected

to the recommended mains

* The fuses must be dimensioned for the rated output current of the device and a

voltage strength of 1000 V DC.

5.3.2 DC-voltage supply

With

supply into the DC bus, energy act. value is also

possible. If the drive is in the generator mode (braking), the
absorbed energy will be passed to the DC

A brake

is then often not necessary.

Motor

P E

DC

%

The fuses must be dimensioned for the rated output current of the device

and a voltage strength of 1000 DC.

36