Technical data, General data and operating conditions – Lenze E82EV 8200 vector 15kW-90kW User Manual

Page 116

Advertising
background image

Technical data

General data and operating conditions

3

l

116

EDK82EV903 DE/EN/FR 5.1

Ambient conditions

Climatic conditions

Storage

IEC/EN 60721−3−1

1K3 (−25 ... +60 °C)

< 6 months

1K3 (−25 ... +40 °C)

> 6 months
> 2 years: form the DC bus
capacitors

Transport

IEC/EN 60721−3−2

2K3 (−25 ... +70 °C)

Operation

2.2 ... 11 kW

IEC/EN 60721−3−3

3K3 (−10 ... +55 °C)
> +40 °C: reduce the rated output current by 2.5 %/°C.

15 ... 90 kW

3K3 (0 ... +50 °C)
> +40 °C: reduce the rated output current by 2.5 %/°C.

Pollution

IEC/EN 61800−5−1

Degree of pollution 2

Site altitude

< 4000 m amsl
> 1000 m amsl: reduce the rated output current by
5 %/ 1000 m.

Electrical

AC mains connection

Max. mains voltage range

E82xV251K2... and E82xV371K2...

1/N/PE 180 V − 0 % ... 264 V + 0 %

E82xV551K2... to E82xV752K2...

1/N/PE 180 V − 0 % ... 264 V + 0 % or
3/PE 100 V − 0 % ... 264 V + 0 %

E82xV551K4... to E82xV903K4...

3/PE 320 V − 0 % ... 550 V + 0 %

Mains frequency

45 Hz − 0 % ... 65 Hz + 0 %

Mains system

With earthed neutral (TT, TN): unrestricted operation
permitted
Other mains systems: observe restrictions described in the
system manual, chapter about project planning

Operation on public
supply systems

EN 61000−3−2

Limitation of harmonic currents

Total power drawn from
the mains

Compliance with the
requirements

1)

< 1 kW

With mains choke.

> 1 kW

Without additional measures.

1)

The additional measures described only ensure that the controllers comply

with the requirements of EN 61000−3−2. Compliance of the machine/system
with the requirements is in the responsibility of the machine/system
manufacturer!

DC mains connection

Max. mains voltage range

450 V − 0 % ... 740 V + 0 %

E82xV251K2... and E82xV371K2...

not possible

E82xV551K2... to E82xV752K2...

140 V − 0 % ... 370 V + 0 %

E82xV551K4... to E82xV903K4...

450 V − 0 % ... 775 V + 0 %

Operation at rated power

450 V − 0 % ... 625 V + 0 %

Operation at an increased rated
power

Operating conditions

The DC voltage must be symmetrical to PE.
The controller will be destroyed if the +U

G

conductor or −U

G

conductor is earthed.