Motor connection, Electrical installation, Danger – Lenze E82EV 8200 vector 15kW-90kW User Manual

Page 146: 4 motor connection

Advertising
background image

Electrical installation

Motor connection

5

l

146

EDK82EV903 DE/EN/FR 5.1

5.3.4

Motor connection

{

Danger!

ƒ

All control terminals only have basic insulation (single isolating distance)
after connecting a PTC thermistor or a thermal contact.

ƒ

Protection against accidental contact in case of a defective isolating
distance is only guaranteed through external measures, e. g. double
insulation.

U

V

W

PE

T1

T2

PE

U, V, W,

PE

5 Nm
44 lb-in

M 6

T1

T2

2,5 Nm

22.1 lb-in

g

k

2,5 Nm

22.1 lb-in

2

1

g

f

k

e

PE

PE

M

3~

M

3~

PTC

PE

PES

PE

U

V

W

T1

T2

J>

PES

PES

PES

PES

PES

PES

8200vec285

Use low−capacitance motor cables! (core/core

£ 140 pF/m, core/shield £ 230 pF/m)

The shorter the motor cable, the better the drive behaviour!
PES

HF shield termination by PE connection through shield clamp.

T1, T2

Terminals of motor temperature monitoring with PTC thermistor or thermal
contact (NC contact).
Lay a separate cable (shielded) to X2/T1 and X2/T2 for motor temperature
monitoring.
Activate motor temperature monitoring with C0119 (e.g. C0119 = 1)!
Lay the control and mains cables separately from the motor cable!

Cable cross−sections U, V, W, PE

8200 vector

mm

2

AWG

E82xV153K4B

10

8

СССССССССС

E82xV223K4B

СССССССССС

16

6

СССССССССС

СССССССССС

E82xV303K4B

СССССССССС

СССССССССС

25

3