Fuses and cable cross-sections according to ul, Fuses and cable cross−sections according to ul, Electrical installation – Lenze E82EV 8200 vector 15kW-90kW User Manual

Page 145

Advertising
background image

Electrical installation

Standard devices in the power range 15 ... 30 kW

Fuses and cable cross−sections according to UL

5

l

145

EDK82EV903 DE/EN/FR 5.1

5.3.3

Fuses and cable cross−sections according to UL

Supply conditions

Range

Description

Fuses

l

Only according to UL 248

l

Mains short−circuit current up to 5000 A

rms

: All classes permissible

l

Mains short−circuit current up to 50000 A

rms

: Only classes "J", "T" or "R" permissible

Cables

l

Only in accordance with UL

l

The cable cross−sections specified in the following apply under the following conditions:
– Conductor temperature < 75 °C
– Ambient temperature < 40 °C

Observe all national and regional regulations!

Operation with increased rated power

Operation at an increased rated power is not UL−certified.

Operation at rated power

8200 vector

Rated fuse current / cable cross−section

Fuse

Circuit−breaker

Type

L1, L2, L3, PE

Type

L1, L2, L3, PE

Type

[A]

[AWG]

[A]

[AWG]

Mains 3/PE AC 400/500 V − operation without mains choke/mains filter

E82xV153K4B

Operation only permitted with mains choke or mains filter

E82xV223K4B

E82xV303K4B

Mains 3/PE AC 400/500 V − operation with mains choke/mains filter

E82xV153K4B

35

8

E82xV223K4B

50

6

E82xV303K4B

80

4

Advertising