Parameter setting with e82zbc keypad, Commissioning – Lenze E82EV 8200 vector 15kW-90kW User Manual

Page 168

Advertising
background image

Commissioning

Parameter setting with E82ZBC keypad

7

l

168

EDK82EV903 DE/EN/FR 5.1

7.2

Parameter setting with E82ZBC keypad

,

Read the documentation for the keypad before starting work!

After every mains switching, or after connection of the keypad during operation, the 10
codes that have been defined in code C0517 are immediately available.

By default, the user menu contains all codes required for commissioning a standard
application with linear V/f characteristic control:

Code

Designation

Lenze setting

C0050

Output frequency

Display: output frequency without slip compensation

C0034

Range of setpoint selection

0

Standard I/O

X3/8: 0 ... 5 V / 0 ... 10 V / 0 ... 20 mA

Application I/O

X3/1U: 0 ... 5 V / 0 ... 10 V
X3/2U: 0 ... 5 V / 0 ... 10 V

C0007

Fixed configuration digital
inputs

0

E4

E3

E2

E1

CW/CCW

DCB

JOG2/3

JOG1/3

Clockwise

rotation/counte

r−clockwise

rotation

DC injection

brake

Selection fixed setpoints

C0010

Minimum output frequency

0.00 Hz

C0011

Maximum output frequency

50.00 Hz

C0012

Acceleration time main
setpoint

5.00 s

C0013

Deceleration time main
setpoint

5.00 s

C0015

V/f rated frequency

50.00 Hz

C0016

V

min

boost

device−dependent

C0002

Parameter set management

Re−establish delivery status; transfer parameter sets by
means of the keypad; save, load, or copy own basic settings

)

Note!

Via C0002 "Parameter set transfer/establishing the delivery status", you can
transfer configurations from drive controller to drive controller by means of
the keypad, or re−establish the delivery status by loading the Lenze setting
(e. g. if you’ve lost track during parameterising).