Extensions for automation – Lenze E82EV 8200 vector 15kW-90kW User Manual

Page 164

Advertising
background image

Extensions for automation

Modules
Mounting and dismounting function modules

6

l

164

EDK82EV903 DE/EN/FR 5.1

Dismounting

8200vec622

The following worksteps apply to the interfaces FIF I (at the top) and FIF II (at the bottom).

1. Disconnect the drive controller from mains and wait at least 3 minutes!

2. Carefully press the clip

0 upwards and remove the function module 3.

3. Plug the FIF cover

2 to the terminals of the interface.

– Make sure that the pins of the FIF interface are plugged correctly in the sockets of

the FIF cover and are not bent.

– Without the FIF cover, the controller is inhibited.

4. Plug on the blanking cover

1.

5. Push the blanking cover

1 until the clip 0 locks into place.

– If no function module is plugged on, the controller without FIF cover

2 and

blanking cover

1 must not be commissioned (dangerous electrical voltage at the

FIF interface).

Advertising