Extensions for automation

Modules
Wiring of controller inhibit (CINH) when two function modules are operated

6

l

166

EDK82EV903 DE/EN/FR 5.1

6.1.3

Wiring of controller inhibit (CINH) when two function modules are operated

)

Note!

ƒ

Both terminals X3/28 of the interface FIF I and FIF II are evaluated internally
via an AND−operation.

ƒ

The following illustrations show possible methods of wiring. Considering
the AND−operation of both terminals X3/28, wiring can be adapted to your
application.

Internal DC voltage supply

FIF I

39 7

+20V

28

20

X3

GND3 GND1

62

9 7 20 28 E1 E2 E3 E4 39 A1 59

E82ZAFSC010

E82ZAFx

FIF II

+20V

+5V

X3

GND1

GND2

0.5...0.6 Nm

4.4...5.3 lb-in

X3

PES

PES

0

8200vec262

0

For function modules with terminals X3/7 and X3/39: Install a wire jumper between X3/7
and X3/39

PES

HF shield termination by large−surface connection to PE
Wiring of the other terminals:

^ Mounting instructions of the function modules

External voltage supply

FIF I

39 7

+20V

28

20

X3

GND2 GND1

62

9 7 20 28 E1 E2

+

E3 E4 39 A1 59

E82ZAFSC010

E82ZAFx

FIF II

+20V

24 V ext.

(

+30 V +0 %, max. 120 mA)

+12 V -0 % ...

+5V

X3

GND1

GND2

0.5...0.6 Nm

4.4...5.3 lb-in

X3

PES

PES

0

8200vec263

0

For function modules with terminals X3/7 and X3/39: Install a wire jumper between X3/7
and X3/39

PES

HF shield termination by large−surface connection to PE
Wiring of the other terminals:

^ Mounting instructions of the function modules