Electrical installation, Danger – Lenze E82EV 8200 vector 15kW-90kW User Manual

Page 158

Advertising
background image

Electrical installation

Connection of relay output K

SR

5

l

158

EDK82EV903 DE/EN/FR 5.1

Technical data

Terminal

Description

Range

Values

X3.1/K32
X3.1/K31
X3.1/33
X3.1/34

Safety relay K

SR

1st disconnecting path

Coil voltage at +20 °C

DC 24 V (20 ... 30 V)

Coil resistance at +20 °C

823

W ±10 %

Rated coil power

Approx. 700 mW

Max. switching voltage

AC 250 V, DC 250 V (0.45 A)

Max. switching capacity, AC

1500 VA

Max. switching current (ohmic load)

AC 6 A (250 V), DC 6 A (50 V)

Recommended minimum load

> 50 mW

Max. operating frequency

6 switching operations per minute

Mechanical service life

10

7

switching cycles

Electrical service life

at AC 250 V
(ohmic load)

10

5

switching cycles at 6 A

10

6

switching cycles at 1 A

10

7

switching cycles at 0.25 A

at DC 24 V
(ohmic load)

6 × 10

3

switching cycles at 6 A

10

6

switching cycles at 3 A

1.5 × 10

6

switching cycles at 1 A

10

7

switching cycles at 0.1 A

Terminal data

Cable type

Wire end ferrule

Cable cross−section

Tightening torque Stripping length

Directly
coupled
to the
mains

2.5 mm

2

(AWG 14)

0.5 ... 0.6 Nm

(4.4 ... 5.3 lb−in)

5 mm

Flexible With plastic sleeve

2.5 mm

2

(AWG 14)

Wiring

}

Danger!

Faulty operation in case of earth faults possible
The correct functioning of the safety function is not ensured if an earth fault
occurs.
Possible consequences:

ƒ

A failure of the safety function can lead to death, severe injuries or damage
to material.

Protective measures:
The electrical reference point for the coil of the safety relay K

SR

must be

connected to the PE conductor system (EN 60204−1, paragraph 9.4.3)!