Commissioning, Important codes for quick commissioning – Lenze E82EV 8200 vector 15kW-90kW User Manual

Page 181

Advertising
background image

Commissioning

Important codes for quick commissioning

7

l

181

EDK82EV903 DE/EN/FR 5.1

IMPORTANT

Possible settings

Code

Selection

Lenze

Name

No.
C0034*

v
uSEr

Range of
setpoint
selection
Standard I/O
(X3/8)

Observe switch position of the
function module!

0

0

Unipolar voltage 0 ... 5 V / 0 ... 10 V
Current 0 ... 20 mA

1

Current 4 ... 20 mA

Reversal of rotation direction only
possible with a digital signal.

2

Bipolar voltage −10 V ... +10 V

l

Minimum output frequency
(C0010) not effective

l

Individually adjust offset and gain

3

Current 4 ... 20 mA open−circuit monitored

TRIP Sd5 if I < 4 mA
Reversal of rotation direction only
possible with a digital signal.

C0034*

v

(A)

uSEr

Range of
setpoint
selection
Application I/O

Observe jumper position of the
function module!

1 X3/1U, X3/1I

0

0

Unipolar voltage 0 ... 5 V / 0 ... 10 V

2 X3/2U, X3/2I

1

Bipolar voltage −10 V ... +10 V

Minimum output frequency (C0010)
not effective

2

Current 0 ... 20 mA

3

Current 4 ... 20 mA

Reversal of rotation direction only
possible with a digital signal.

4

Current 4 ... 20 mA open−circuit monitored

Reversal of rotation direction only
possible with a digital signal.
TRIP Sd5 at I < 4 mA

C0037

JOG1

20.00 −650.00

{0.02 Hz}

650.00 JOG = fixed setpoint

Additional fixed setpoints

ðC0440

C0038

JOG2

30.00 −650.00

{0.02 Hz}

650.00

C0039

JOG3

40.00 −650.00

{0.02 Hz}

650.00

C0050*

uSEr

Output
frequency
(MCTRL1−NOUT)

−650.00

{Hz}

650.00 Read only: Output frequency without

slip compensation

C0087

Rated motor
speed

à

300

{1 rpm}

16000

à

Device−dependent

C0088

Rated motor
current

à

0.0

0.1 (A)

650.0

à

Device−dependent

0.0 ... 2.0 x rated output current of the
controller

C0089

Rated motor
frequency

50

10

{1 Hz}

960

C0090

Rated motor
voltage

à

50

{1 V}

500

à

230 V for 230 V controllers,
400 V for 400 V controllers

C0091

Motor cos

а

0.40

{0.1}

1.0

а

Device−dependent

C0119

v

Configuration of
motor
temperature
monitoring (PTC
input) / earth
fault detection

0

0

PTC input inactive

Earth fault detection
active

l

Configure signal output in C0415

l

If several parameter sets are used,
monitoring has to be set
separately for every parameter set.

l

Deactivate earth fault detection if
the earth fault detection is
actuated unintentionally.

l

If the earth fault detection is
activated, the motor starts with a
delay of approx. 40 ms after
controller enable has been set.

1

PTC input active,
TRIP effected

2

PTC input active,
warning effected

3

PTC input inactive

Earth fault detection
inactive

4

PTC input active,
TRIP effected

5

PTC input active,
warning effected