V/f characteristic control, Commissioning – Lenze E82EV 8200 vector 15kW-90kW User Manual

Page 169

Advertising
background image

Commissioning

Parameter setting with E82ZBC keypad

V/f characteristic control

7

l

169

EDK82EV903 DE/EN/FR 5.1

7.2.1

V/f characteristic control

The following instructions apply to controllers equipped with a standard−I/O function
module and a three−phase AC motor which has been selected according to a power−based
assignment.

Switch−on sequence

Comment

1.

Connect keypad

2.

Ensure that controller inhibit is active after mains connection

Terminal X3/28 = LOW

3.

Switch on the mains

4.

The keypad is in "Disp" mode after approx. 2 s and indicates the
output frequency (C0050)

The USEr menu is active

5.

Change to the

f mode to configure the basic settings for your

drive

Blinking on the display: 0050

6.

Adapt the voltage/current range for the analog setpoint selection
(C0034)
Lenze setting: −0−, (0 ... 5 V/0 ... 10 V/0 ... 20 mA)

Set the DIP switch on the standard I/O to the same
range (see Mounting Instructions for the standard
I/O)

7.

Adapt the terminal configuration to the wiring (C0007)
Lenze setting: −0−, i. e.
E1: JOG1/3 fixed setpointselection
E2: JOG2/3
E3: DCB DC brake
E4: CW/CCW rotation

8.

Set the minimum output frequency (C0010)
Lenze setting: 0.00 Hz

9.

Set the maximum output frequency (C0011)
Lenze setting: 50.00 Hz

10.

Set the acceleration time T

ir

(C0012)

Lenze setting: 5.00 s

11.

Set the deceleration time T

if

(C0013)

Lenze setting: 5.00 s

12.

Set the V/f−rated frequency (C0015)
Lenze setting: 50.00 Hz

13.

Set the V

min

boost (C0016)

Lenze setting: Depending on the controller type

The Lenze setting is suitable for all common
applications

14.

If you want to change the settings, go to the ALL menu

For instance activate JOG frequencies (C0037,
C0038, C0039) or motor temperature monitoring
(C0119)

When all settings are complete:

15.

Select setpoint

E.g. via potentiometer at terminals 7, 8, 9

16.

Enable the controller

Terminal X3/28 = HIGH

17.

The drive is now running.

If the drive does not start, additionally press