Mounting in "cold plate" technique, Mechanical installation – Lenze E82EV 8200 vector 15kW-90kW User Manual

Page 123

Advertising
background image

Mechanical installation

Standard devices in the power range 15 ... 30 kW

Mounting in "cold plate" technique

4

l

123

EDK82EV903 DE/EN/FR 5.1

4.2.3

Mounting in "cold plate" technique

For this mounting variant you require the controller type E82CV...

The following points are important for safe and reliable operation of the controller:

ƒ

Good thermal connection to the cooler
– The contact surface between the collective cooler and the controller must be at

least as large as the cooling plate of the controller.

– Plane contact surface, max. deviation 0.05 mm.
– When attaching the collective cooler to the controller, make sure to use all

specified screw connections.

ƒ

Observe the thermal resistance R

th

given in the table. The values are valid for

controller operation under rated conditions.

Power to be dissipated by the heatsink

Cooling path of heatsink − ambience

8200 vector

P

v

[W]

R

th

[K/W]

СССССС

СССССС

E82CV153K4B

СССССССССССС

СССССССССССС

287

ССССССССССССС

ССССССССССССС

£ 0.085

СССССС

E82CV223K4B

СССССССССССС

427

ССССССССССССС

£ 0.057

Ambient conditions

ƒ

The rated data and the derating factors at increased temperature also apply to the
ambient temperature of the drive controllers.

ƒ

Temperature at the cooling plate of the drive controller: max. 75 °C.