Electrical installation

Standard devices in the power range 75 ... 90 kW

Mains connection

5

l

151

EDK82EV903 DE/EN/FR 5.1

5.5

Standard devices in the power range 75 ... 90 kW

5.5.1

Mains connection

(

Stop!

ƒ

Only connect the controller to the permitted mains voltage (

^ Technical

data). A higher mains voltage destroys the controller!

ƒ

Some controllers may only be actuated with a mains choke or mains filter.
This requirement can differ with regard to operation at rated power and
operation at an increased rated power.

ƒ

The leakage current to earth (PE) is > 3.5 mA. In accordance with
EN 61800−5−1 a fixed installation is required. The PE conductor has to be
designed double.

0

L1

L2
L3

N
PE

+UG

-UG

Z1

PE

L1

L2

L3

3/PE AC 400V

T2

T1

L2 L3

L1

3

3

4

L1 L2 L3

+UG

PE

l

3/PE AC 400V

-UG

L1, L2, L3

+UG, -UG

PE

30 Nm

264 lb-in

M10

PE

L1

L2

L3

+UG

PE

l

L1’ L2’ L3’
Gerät / Load

L1 L2 L3 PE
Netz / Line

3/PE AC 400V

Z1

-UG

L1, L2, L3

+UG, -UG

PE

30 Nm

264 lb-in

M10

PE

3

2

T1
T2

2,5 Nm

22.1 lb-in

L1 L2 L3

+UG

PE

l

-UG

L1 L2 L3

3/PE AC 400V

PE

+UG, -UG
PE

M10

30 Nm
264 lb-in

E82EV753K4:
6-12 Nm (53.1-106.2 lb-in)
E82EV903K4:
10-20 Nm (88.5-177 lb-in)

L1, L2,

L3

3

4

1

J>

8200vec290

0

Connection for mains choke

1

Connection for footprint mains filter

2

Connection for built−on mains filter

3

Connection for braking unit (

^ Documentation of braking unit)

4

Temperature monitoring connection for mains filter (thermal contact)

Z1

Mains choke/mains filter