Commissioning

Parameter setting with the XT EMZ9371BC keypad
V/f characteristic control

7

l

172

EDK82EV903 DE/EN/FR 5.1

7.3

Parameter setting with the XT EMZ9371BC keypad

,

Read the documentation for the keypad before starting work!

)

Note!

In the "Diagnostic" menu you can monitor the most important drive
parameters

7.3.1

V/f characteristic control

The following instructions apply to controllers equipped with a standard−I/O function
module and a three−phase AC motor which has been selected according to a power−based
assignment.

Switch−on sequence

Comment

1.

Plug in the keypad

2.

Ensure that controller inhibit is active after mains connection

Terminal X3/28 = LOW

3.

Switch on the mains

4.

After approx. 3 s the keypad is in the operating level and displays
the output frequency (C0050) and the device utilisation (C0056)

5.

For quick commissioning you select the "Quick start" menu

The submenu "V/f quick" contains the codes which
you require for commissioning a standard application.
The digital inputs are configured in the Lenze setting:
X3/E1, X3/E2: activation of fixed setpoints (JOG)
X3/E3: activation of DC injection brake (DCB)
X3/E4: CW rotation/CCW rotation

A

Change the menu level with

V

B

Change to the "Quick start" menu and from there to the
submenu "V/f quick" with

z z Z z

C

Change to the code level with

Z to parameterise your drive

6.

Adapt the voltage/current range for the analog setpoint selection
(C0034)
Lenze setting: 0, (0 ... 5 V/0 ... 10 V/0 ... 20 mA)

Set the DIP switch on the standard I/O to the same
range (see Mounting Instructions for the standard I/O)

7.

If required, adapt the fixed setpoints JOG.

A

JOG 1 (C0037)
Lenze setting: 20 Hz

Activation:
X3/E1 = HIGH, X3/E2 = LOW

B

JOG 2 (C0038)
Lenze setting: 30 Hz

Activation:
X3/E1 = LOW, X3/E2 = HIGH

C

JOG 3 (C0039)
Lenze setting: 40 Hz

Activation:
X3/E1 = HIGH, X3/E2 = HIGH

8.

Set the minimum output frequency (C0010)
Lenze setting: 0.00 Hz

9.

Set the maximum output frequency (C0011)
Lenze setting: 50.00 Hz

10.

Set the acceleration time T

ir

(C0012)

Lenze setting: 5.00 s

11.

Set the deceleration time T

if

(C0013)

Lenze setting: 5.00 s

12.

Set the V/f−rated frequency (C0015)
Lenze setting: 50.00 Hz

13.

Set the V

min

boost (C0016)

Lenze setting: depends on the controller type

The Lenze setting is suitable for all common
applications

14.

Activate the motor temperature monitoring (C0119) if you have
connected a PTC or thermal contact to terminal X2.2
Lenze setting: switched off

Possible settings

(

181)

When all settings are complete:

15.

Select setpoint

E.g. via potentiometer at terminals 7, 8, 9