Mechanical installation – Lenze E82EV 8200 vector 15kW-90kW User Manual
Page 127
![background image](/manuals/565990/127/background.png)
Mechanical installation
Standard devices with a power of 45 kW
Mounting with fixing brackets (standard)
l
127
EDK82EV903 DE/EN/FR 5.1
Controller variant "3xx" (with fully mounted footprint filter)
For this mounting variant you require controller type E82EVxxxK4B3xx.
2
3
1
³
150 mm
a
l
b1
³
100 mm
k
c
c1
m
g
d1
d2
d
b
e
a
M 8
g
f
e
L
M 8
max. 15 mm
0
³ 50 mm
³ 50 mm
18 Nm
159.3 lb-in
8200vec298
Loosen both screws to be able to remove the housing cover. The assembly kit is located under
the housing cover.
Installation of mounting angles
Dimensions
0
Arrange the controllers side by side with spacing to be able to disassemble the eyebolts.
Dimensions [mm]
8200 vector
integr. mains
filter
2)
a
b
b1
c
c1
d
d1
d2
e
1)
g
k
m
E82EV453K4B3xx
E82ZN45334B230
340
619
510
283 28.5 580
38
532
375
11
28
18
1)
If the function module is attached: observe mounting clearance and cable bending radius. The terminals of function
modules in PT design protrude above the housing by 8 mm.
2)
The integrated mains filters are only designed for controller operation at rated power. Different filters with different
dimensions are possible (
^ 140
).