MODEL

OUTPUT

NUMBER

INPUT CURRENT

POWER

CURRENT

(NOTE 1)

HP

kW

PHASE

(AMPS)

(kVA)

(AMPS)

0 - 400 / 460 Vac

STD

THRU

SD405

0.5

0.37

3

1.6 / 1.4

1.1

1.3 / 1.1

26

N/A

SD410

1

0.75

3

2.9 / 2.5

2.1

2.4 / 2.1

40

12

SD415

1.5

1.1

3

4.0 / 3.6

3.0

3.4 / 3.0

56

13

SD420

2

1.5

3

4.6 / 4.0

3.3

3.9 / 3.4

67

14

SD430

3

2.2

3

6.2 / 5.4

4.5

5.5 / 4.8

100

19

SD450

5

3.7

3

9.8 / 8.6

7.1

8.7 / 7.6

168

22

SD475

7.5

5.5

3

14.2 / 12.4

10.3

12.6 / 11.0

254

29

SD4100

10

7.5

3

18.1 / 15.8

13.1

16.1 / 14.0

310

37

SD4150

15

11

3

27 / 24

20.0

24 / 21

390

42

SD4200

20

15

3

35 / 31

25.8

31 / 27

530

57

SD4250

25

18.5

3

44 / 38

31.6

39 / 34

648

72

0 - 460 / 575 Vac

SD510

1

0.75

3

2.2 / 2.0

1.9 / 2.0

1.9 / 1.7

40

12

SD520

2

1.5

3

4.0 / 3.5

3.3 / 3.6

3.4 / 3.0

67

13

SD530

3

2.2

3

4.7 / 4.7

3.9 / 4.8

4.2 / 4.2

100

14

SD550

5

3.7

3

7.4 / 7.4

6.1 / 7.5

6.6 / 6.6

168

19

SD575

7.5

5.5

3

11.2 / 11.2

9.3 / 11.4

9.9 / 9.9

254

29

SD5100

10

7.5

3

13.7 / 13.7

11.4 / 14.0

12.2 / 12.2

310

37

SD5150

15

11

3

22 / 22

18.3 / 22.5

19.0 / 19.0

390

42

SD5200

20

15

3

27 / 27

22.4 / 27.6

24 / 24

530

57

SD5250

25

18.5

3

31 / 31

25.8 / 31.7

27 / 27

648

72

NOTE 1: See Section 3.0 for model number breakdown.

NOTE 3: The higher current ratings are for 400 Vac input and the lower current ratings are for 480 Vac input.

NOTE 4: The higher current ratings are for 480 Vac input and the lower current ratings are for 590 Vac input.

NOTE 5: STD = standard unit; THRU = through-hole mount unit. Values are worst-case (not typical) for 6kHz

carrier frequency at full speed and full load.

(NOTE 5)

SD500 SERIES (NOTE 4)

480 / 590 Vac

HEAT LOSS

(WATTS)

SD400 SERIES (NOTE 3)

400 / 480 Vac

FOR MOTORS

INPUT (50-60 Hz)

RATED