DNET Par. ID 25 - SPEED REFERENCE:

0 - Local speed reference (SCD drive speed selection: keypad, presets, analog)
1 - Network speed reference
Object Map - AC Drive Object 0x2A-1-4

NOTE: Parameter IDs 20-25 will reset to 0 when power is cycled or the drive is reset.

DNET Par. ID 26 - NETWORK COMMAND FREQUENCY: Sets the drive command frequency
if parameter ID #25 is set to NETWORK REFERENCE (0.1 Hz resolution).

DNET Par. ID 27 - CONTROL SOURCE (READ ONLY)

0 - Local control
1 - Control from the Network
Object Map - Control Supervisor Object 0x29-1-15

DNET Par. ID 28 - SPEED REFERENCE SOURCE (READ ONLY)

0 - Local speed reference
1 - Network speed reference
Object Map - AC Drive Object 0x2A-1-29

DNET Par. ID 29 - DRIVE ACTUAL DIRECTION (READ ONLY)

0 - Forward
1 - Reverse

DNET Par. ID 30 - RUN STATUS (READ ONLY): See table below:

DNET Par. ID 31 - SPEED SOURCE (READ ONLY): See table below:

NO.

NO.

NO.

STATUS

0

FAULT LOCKOUT

4

DC BRAKE

8

DECELERATION

1

FAULT

5

RUN AT 0 Hz

9

CURRENT LIMIT

2

START PENDING

6

RUN

10

DECEL OVERRIDE

3

STOP

7

ACCELERATION

11

LOWER ON SEQUENCE

STATUS

STATUS

RUN STATUS

NO.

NO.

NO.

0

KEYPAD

5

PRESET SPEED #3

10

JOG SPEED

1

0 - 10 VDC

6

PRESET SPEED #4

11

MOP SPEED

2

4 - 20 mA

7

PRESET SPEED #5

12

DEVICENET

3

PRESET SPEED #1

8

PRESET SPEED #6

4

PRESET SPEED #2

9

PRESET SPEED #7

SOURCE

STATUS

SPEED SOURCE

STATUS