Lenze SCD Series User Manual

Page 81

Advertising
background image

78

If Attribute #5 NET CONTROL is set to 1, the RUN and STOP events are triggered according to the
following event table:

NOTE: If ACT PARAMETER #17 DIRECTION is set to FORWARD ONLY, the drive will not be
able to run in the reverse direction.

ATTRIBUTE ID ACCESS RULE

NAME

DATA TYPE

VALUE

1

GET

NO. OF SUPPORTED

USINT

16

ATTRIBUTES

2

GET

ATTRIBUTE LIST

ARRAY

3

GET / SET

RUNFWD

BOOL

0 to 1

4

GET / SET

RUNREV

BOOL

0 to 1

5

GET / SET

NETCTRL

BOOL

0 to 1

6

GET

STATE

UINT

3 = Ready

4 = Enabled

7 = Faulted

7

GET

RUNNINGFWD

BOOL

0 to 1

8

GET

RUNNINGREV

BOOL

0 to 1

9

GET

READY

BOOL

0 to 1

10

GET

FAULTED

BOOL

0 to 1

11

GET

WARNING

UINT

0 (Not Supported)

12

GET / SET

FAULTRST

BOOL

0 to 1

13

GET

FAULT CODE

UINT

0 to 65535

15

GET

CTRLFROMNET

USINT

0 to 1

16

GET / SET

ACTION ON LOSS

USINT

0 = Fault

OF DEVICENET

1 = Ignore Comm. Fault

2 = AC Tech Specific

17

GET / SET

FORCE TRIP

BOOL

0 to 1

INSTANCE 1

CONTROL SUPERVISOR CLASS ATTRIBUTES

The drive shows the "nF" fault on the LED display

ATTRIBUTE RUN FWD

ATTRIBUTE RUN REV

TRIGGER EVENT

RUN TYPE

0

0

STOP

N/A

0 --> 1

0

RUN

RUN FORWARD

0

0 --> 1

RUN

RUN REVERSE

0 --> 1

0 --> 1

NO ACTION

N/A

1

1

NO ACTION

N/A

1 --> 0

1

RUN

RUN REVERSE

1

1 --> 0

RUN

RUN FORWARD