If the power-up or reset sequence fails, the SCD drive will enter DeviceNet failure mode. In that case,
the drive will not be accessible to the network, but can still be operated in terminal mode. This failure
state is indicated in parameter C10 DIAGNOSTIC by number "093" (refer to Section B.6 and B.7 for
details on parameter C10).

B.3

BASIC MODE OF OPERATION

The SCD Series Drive can operate under DeviceNet

TM

control in any terminal configuration shown in

Section 11.0 of this manual. The DeviceNet Master can take control any time by setting the Network
Control bit (attribute 5 in Control Supervisor Object - see supported Objects and attributes on following
pages).

B.3.1

SAMPLE SETUP AND WIRING FOR DEVICENET

TM

CONTROL

This example uses Explicit or I/O Polled messaging for Run Forward/Reverse and speed control.

NOTE: Terminal 1 must be closed to terminal 4 in order to start the drive through the DeviceNet

TM

interface.

PARAMETER SET-UP:

Parameters can be setup using the drive keypad, EPM Programmer, or DeviceNet

TM

configuration tool

(for example RSNetWorx

TM

) that uses EDS file provided by AC Technology.

The following parameters should be set as a minimum:

P17

ROTATION DIRECTION - Set this parameter to FORWARD & REVERSE (02) if operation
in both directions is required.

P85

MOTOR NOMINAL SPEED AT RATED FREQUENCY (RPM)

P86

MOTOR RATED CURRENT (0.1 A)

P87

MOTOR RATED VOLTAGE (V)

P88

MOTOR RATED FREQUENCY (Hz)

P89

DRIVE RATED CURRENT (0.1 A)

P90

DRIVE RATED VOLTAGE (V)

C00

DEVICENET NODE ADDRESS (0 - 63)

C01

DEVICENET BAUD RATE (125, 250, 500 kbps)

C03

DEVICENET OUTPUT ASSEMBLY SELECTION - Set this parameter to select output
assembly for Polled connection. The following selections are available:

1 = "1 Basic Contactor"
2 = "2 Basic Overload"
3 = "3 Basic Motor Starter"
4 = "4 Ext. Contactor"
5 = "5 Ext. Motor Starter"
6 = "20 Basic Speed Ctrl"
7 = "21 Ext. Speed Ctrl RPM"
8 = "100 Ext.Speed Ctrl Hz"
9 = "103 Preset Speed Ctrl"