DNET ID 126 ACT Par 86 MOTOR RATED CURRENT
DNET ID 127 ACT Par 87 MOTOR RATED VOLTAGE
DNET ID 128 ACT Par 88 MOTOR RATED FREQUENCY
DNET ID 129 ACT Par 89 DRIVE RATED CURRENT
DNET ID 130 ACT Par 90 DRIVE RATED VOLTAGE

DNET Par. ID 6 - COMMANDED FREQUENCY (READ ONLY): Actual commanded frequency
(speed) of the drive (0.1 Hz resolution).

DNET Par. ID 7 - PRESENT FAULT DNET CODE (READ ONLY): Shows the current fault code.
Refer to the table in Section B.5.9.

DNET Par. ID 8 - PRESENT FAULT NAME (READ ONLY): See the table below:

DNET Par. ID 9 through 16 - Reserved.

DNET Par. ID 17 - BUS OFF ERROR: Determines how the Communication Section processes a
CAN Bus OFF condition.

0 - Hold CAN chip in bus off state when bus off is detected.
1 - Tries to reset the CAN and continue communication.

DNET Par. ID 18 - BUS OFF COUNT: Number of times the CAN peripheral went into bus off state.
Counter maximum value is 255. Any write into this parameter resets the counter to 0.

DNET Par. ID 19 - DEVICENET IDLE MODE: This parameter is used to set the action the SCD
drive should perform when the connection is closed (set to idle state) and drive is still in DNET
control.

0 - STOP the drive if IDLE mode
1 - Hold last state if IDLE mode (WARNING! Make sure it is safe to operate this way!)

NO.

NO.

NO.

0

NO FAULT

10

INTERNAL 1 EPM

20

SINGLE PHASE INPUT

1

OUTPUT FAULT

11

INTERNAL 2

21

INCOMPATIBLE EPM

2

HIGH TEMP.

12

INTERNAL 3

22

DYNAMIC BRAKE

3

HIGH BUS VOLTAGE

13

INTERNAL 4

23

DEVICENET FAULT

4

LOW BUS VOLTAGE

14

INTERNAL 5

24

DNET TRIGGER FAULT

5

MOTOR OVERLOAD

15

INTERNAL 6

25

RESERVED

6

CONTROL FAULT

16

INTERNAL 7

26

RESERVED

7

EXTERNAL FAULT

17

INTERNAL 8

27

RESERVED

8

OEM DATA FAILED

18

INTERNAL 9

9

START ERROR

19

INTERNAL 10

FAULT NAME

FAULT NAME

FAULT NAME

PRESENT FAULT NAME