EXTERNAL FAULT: Sets TB-13C as a normally closed external fault input. If TB-13C is
open with respect to TB-4, the drive will fault.

07

Factory Reserved: Equivalent to NONE (01).

08

DB FAULT: Sets TB-13C as a dynamic braking fault input when using the optional dynamic
braking module. When this input is activated by the dynamic braking module, the drive will
trip into a "dF" fault and the motor will coast to a stop. Refer to the manual included with the
Dynamic Braking option.

09

ACCEL/DECEL #2: Selects the acceleration and deceleration time programmed into Parameter
42 - ACCEL/DECEL #2.

P13

TB-15 OPEN COLLECTOR OUTPUT

This selects the status indication for the open-collector output at TB-15, and has the same selections
as Parameter 6 - TB-14 OPEN COLLECTOR OUTPUT.

P14

CONTROL

This selects the source of START/STOP and direction commands.

01

TERMINAL STRIP & DEVICENET: The drive can be controlled from the terminal strip, or
can be controlled using DeviceNet serial communications.

02

DEVICENET ONLY: The drive can only be controlled using DeviceNet serial communications.

P16

UNITS EDITING

This allows parameter and keypad speed editing in whole units or tenths of units above 100. Below
100, the value can always be changed by tenths of units.

01

TENTHS OF UNITS: The value can always be changed by tenths of units (up to a value of
1000). If the ! or " button is pressed and held, the value will change by tenths of units until
the next whole unit is reached, and then the value will change by whole units. Refer to Section
13.1.

02

WHOLE UNITS: The value can be changed by tenths of units until 99.9 is reached. Above
99.9, the value will change in whole unit increments only. Below a value of 100, if the ! or "
button is pressed and held, the value will change by tenths of units until the next whole unit is
reached, and then the value will change by whole units.

P17

ROTATION DIRECTION

01

FORWARD ONLY: The drive will only allow rotation in the forward direction. However,
JOG REVERSE (see Parameter 11) will still operate even if FORWARD ONLY is selected.

02

FORWARD AND REVERSE: The drive will allow rotation in both directions.