B.5.10 AC / DC DRIVE OBJECT - CLASS 0x2A

ATTRIBUTE ID ACCESS RULE

NAME

DATA TYPE

VALUE

1

GET

REVISION

UINT

1

2

GET

NUMBER OF

UINT

1

INSTANCES

1

GET

NO. OF SUPPORTED

USINT

12

ATTRIBUTES

2

GET

ATTRIBUTE LIST

ARRAY

3

GET

AT REFERENCE

BOOL

Speed At Ref

4

GET / SET

NET REFERENCE

BOOL

0 = Local Spd Ref

1 = Net Spd Ref

6

GET

DRIVE MODE

USINT

1=Open Loop Spd Control

7

GET

ACTUAL SPEED

INT

Actual Speed (RPM)

8

GET / SET

SPEED REFERENCE

INT

Speed Reference (RPM)

9

GET

MOTOR PHASE

INT

Actual Current (0.1 A)

CURRENT

15

GET

ACTUAL OUTPUT

INT

Actual Power (W)

POWER

16

GET

INPUT VOLTAGE

INT

(V)

17

GET

OUTPUT VOLTAGE

INT

(V)

29

GET

STATUS OF SPEED

INT

0 = Local Spd Ref

REFERENCE

1 = Net Spd Ref

INSTANCE 1

AC / DC DRIVE CLASS ATTRIBUTES

INSTANCE 0

SERVICE

SERVICE

CODE

CLASS

INSTANCE

NAME

0x0E

YES

YES

Get_Attribute_Single

0x10

NO

YES

Set_Attribute_Single

AC DRIVE CLASS SERVICES

IMPLEMENTED FOR