Lenze SCD Series User Manual

Page 51

Advertising
background image

48

P87

MOTOR RATED VOLTAGE

When using the DeviceNet interface, this must be set to match the nameplate voltage rating of the
motor.

P88

MOTOR RATED FREQUENCY

When using the DeviceNet interface, this must be set to match the nameplate frequency rating of the
motor.

P89

DRIVE RATED CURRENT

When using the DeviceNet interface, this must be set to match the nameplate output current rating of
the drive.

P90

DRIVE RATED VOLTAGE

When using the DeviceNet interface, this must be set to match the nameplate maximum output voltage
rating of the drive.

Example: A 5 Hp, 400/480 Vac SCD drive (SD450) is being used with a 5 Hp, 230/460 Vac, 60 Hz,
1800 RPM motor that is rated 7.1 amps. Parameters 85-90 would be set as follows:

P85

MOTOR RATED RPM

1800 RPM

P86

MOTOR RATED CURRENT

7.1 AMPS

P87

MOTOR RATED VOLTAGE

460 VOLTS

P88

MOTOR RATED FREQUENCY

60 Hz

P89

DRIVE RATED CURRENT

7.6 AMPS

P90

DRIVE RATED VOLTAGE

480 VOLTS

C00

DEVICENET NODE ADDRESS

C01

DEVICENET BAUD RATE

C02

DEVICENET LOSS ACTION

C03

DEVICENET OUTPUT ASSEMBLY SELECTION

C04

DEVICENET INPUT ASSEMBLY SELECTION

C05

DEVICENET CUSTOM INPUT ASSEMBLY WORD 0

C06

DEVICENET CUSTOM INPUT ASSEMBLY WORD 1

C07

DEVICENET CUSTOM INPUT ASSEMBLY WORD 2

C08

DEVICENET CUSTOM INPUT ASSEMBLY WORD 3

C09

DEVICENET MOTOR TYPE

C10

DEVICENET DIAGNOSTICS

NOTE: Refer to Appendix B - DeviceNet Control for more information on Parameters 85-90 and
C00 - C10.