DNET Par. ID 37: Reserved.

DNET Par. ID 38 - KEYPAD COMMAND FREQUENCY: Allows the keypad speed (which is
normally accessed using the V and W buttons on the front of the drive) to be changed through DeviceNet.
This speed can be used as Preset Speed #0 in Output Assembly 103 and Parameter 24.

DNET Par. ID 39: Reserved.

DNET Par. ID 40 - SCD DRIVE PARAMETER VERSION (READ ONLY): Displays the parameter
version number of the drive (example: 322). This is the same number that the drive displays when
power is applied.

DNET Par. ID 41 through 139: Correspond to ACT Parameters 1 through 90 and are described in
Section 15.0 - DESCRIPTION OF PARAMETERS.

DNET Par. ID 140 - DEVICENET NODE ADDRESS (ACT PARAMETER C00): DeviceNet
address 0-63. Does not take effect until power to the drive is cycled.

DNET Par. ID 141 - DEVICENET BAUD RATE (ACT PARAMETER C01)

0 - 125kbps
1 - 250kbps
2 - 500kbps

DNET Par. ID 142 - ACTION ON LOSS OF DEVICENET (ACT PARAMETER C02)

0 - FAULT & STOP - Trigger the 'JF' Network fault if drive is running.
1 - IGNORE (do not do anything)
2 - AC TECH specific - Switch OFF control to TERMINAL and do not do anything (if drive was
running, it will keep running in terminal mode)

WARNING! For settings 1 and 2, make sure it is safe to operate this way!

Object Map - Control Supervisor Object 0x29-1-16

DNET Par. ID 143 - DEVICENET OUTPUT ASSEMBLY SELECTION (ACT PARAM. C03):
Select the output assembly, consumption size, and path for polled I/O connection.

1 = "1 Basic Contactor"

- ODVA SPECIFIED

2 = "2 Basic Overload"

- ODVA SPECIFIED

3 = "3 Basic Motor Starter"

- ODVA SPECIFIED

4 = "4 Ext. Contactor"

- ODVA SPECIFIED

5 = "5 Ext. Motor Starter"

- ODVA SPECIFIED

6 = "20 Basic Speed Ctrl"

- ODVA SPECIFIED

7 = "21 Ext. Speed Ctrl"

- ODVA SPECIFIED

8 = "100 Ext.Speed Ctrl Hz"

- AC TECH specific (Same as Assembly 21, except speed is in Hz)

9 = "103 Preset Speed Ctrl"

- AC TECH specific