30

FACTORY

NO.

PARAMETER NAME

RANGE OF ADUSTMENT

DEFAULT

(NOTE 1)

12

TB-13C FUNCTION

NONE (01), 0-10 VDC (02), 4-20 mA (03),

NONE (01)

SELECT

PRESET SPEED #3 (04), INCREASE FREQ (05),

EXTERNAL FAULT (06), Factory Reserved (07),

DB FAULT (08), ACCEL/DECEL #2 (09)

13

TB-15 OUTPUT

(SEE PARAMETER 6 - TB-14 OUTPUT)

NONE (01)

14

CONTROL

TERMINAL STRIP & DEVICENET (01),

TERMINAL STRIP &

DEVICENET ONLY (02),

DEVICENET (01)

16

UNITS EDITING

TENTHS OF UNITS (01),

WHOLE

WHOLE UNITS (02)

UNITS (02)

17

ROTATION

FORWARD ONLY (01),

FORWARD

FORWARD AND REVERSE (02)

ONLY (01)

19

ACCELERATION TIME

0.1 - 3600.0 SEC

20.0 SEC

20

DECELERATION TIME

0.1 - 3600.0 SEC

20.0 SEC

21

DC BRAKE TIME

0.0 - 3600.0 SEC

0.0 SEC

22

DC BRAKE VOLTAGE

0.0 - 30.0 %

0.0 %

23

MINIMUM FREQUENCY

0.0 - MAXIMUM FREQUENCY

0.0 Hz

24

MAXIMUM FREQUENCY

MINIMUM FREQ - 240.0 Hz (NOTE 2)

60.0 Hz

25

CURRENT LIMIT

30 - 180 % (NOTE 3)

180%

26

MOTOR OVERLOAD

30 - 100 %

100%

27

BASE FREQUENCY

25.0 - 500.0 Hz (NOTE 4)

60.0 Hz

28

FIXED BOOST

0.0 - 30.0 %

1.00%

29

ACCEL BOOST

0.0 - 20.0 %

0.00%

30

SLIP COMPENSATION

0.0 - 5.0 %

0.00%

31-37

PRESET SPEEDS

0.0 - MAXIMUM FREQUENCY

0.0 Hz

38

SKIP BANDWIDTH

0.0 - 10.0 Hz

0.0 Hz

39

SPEED SCALING

0.0 - 6500.0

0

PARAMETER MENU (CONT’D)

NOTE 1:

Factory defaults are shown for a 60 Hz base frequency. See Parameter 48 for 50 Hz base frequency.

NOTE 2:

Maximum setting is 999.9 Hz on drives with High Output Frequency option. Consult the factory.

NOTE 3:

If LINE VOLTAGE is set to LOW, maximum setting is 150%.

NOTE 4:

Maximum setting is 1300.0 Hz (factory default is 999.9) on drives with High Output Frequency option.
Consult the factory.