33

NOTE: If this parameter is changed while the drive is running, the new value will not take effect
until the drive is stopped.

P02

CARRIER FREQUENCY

This sets the switching rate of the output IGBT’s. Increasing the carrier frequency will result in less
audible motor noise. Available settings are: 4 kHz, 6 kHz, 8 kHz, and 10 kHz.

15.0

DESCRIPTION OF PARAMETERS

P01

LINE VOLTAGE SELECTION

This calibrates the drive for the actual applied input voltage, and can be set to HIGH (01) or LOW
(02). Refer to the table below for the proper setting depending on the input voltage.

RATED INPUT

INPUT

APPLIED INPUT

PARAMETER

MODEL

VOLTAGE

PHASE

VOLTAGE

SETTING

SF200Y

208 / 240 Vac

1 or 3

220 - 240 Vac

HIGH (01)

1 or 3

200 - 208 Vac

LOW (02)

SF200

208 / 240 Vac

3

220 - 240 Vac

HIGH (01)

3

200 - 208 Vac

LOW (02)

SF400

400 / 480 Vac

3

440 - 480 Vac

HIGH (01)

3

380 - 415 Vac

LOW (02)

SF500

480 / 590 Vac

3

575 - 600 Vac

HIGH (01)

3

460 - 480 Vac

LOW (02)

PARAMETER

CARRIER

MAXIMUM OUTPUT

AMBIENT OR OUTPUT

SETTING

FREQUENCY

FREQUENCY (NOTE 1)

DERATE (NOTE 2)

01

4 kHz

240.0 Hz (400.0 Hz)

50 C or 100%

02

6 kHz

240.0 Hz (600.0 Hz)

50 C or 100%

03

8 kHz

240.0 Hz (999.9 Hz)

43 C or 92%

04

10 kHz

240.0 Hz (999.9 Hz)

35 C or 82%

NOTE 1: For drives with the High Output Frequency option, the carrier frequency also determines
the maximum output frequency (shown in parenthesis).

NOTE 2: The SCD drive is fully rated up to 6 kHz carrier frequency. If the 8 kHz or 10 kHz carrier
frequency is selected, the drive’s ambient temperature rating OR output current rating must be de-
rated to the value shown in the table above.