Electrical installation, Important notes, Protection of persons – Lenze EMB934x User Manual
Page 101: 5electrical installation
![background image](/manuals/566110/101/background.png)
Electrical installation
Important notes
Protection of persons
5
l
101
EDBMB9340 DE/EN/FR 12.0
5
Electrical installation
5.1
Important notes
5.1.1
Protection of persons
{
Danger!
ƒ
Before working on the regenerative power supply module, check that no
voltage is applied to the power terminals.
– Some power terminals remain live for at least three minutes after mains
disconnection.
ƒ
For controllers in DC−bus operation
– the controller must be inhibited.
– the controller must be separated from the mains.
ƒ
The discharge current to PE is > 3.5 mA; i.e. a fixed installation is required
and PE must be connected according to EN 61800−5−1.
Earth−leakage circuit breaker
We recommend e.l.c.b.s to protect persons and animals (
¶ 104).
Pluggable terminal strips
All pluggable terminals must only be plugged on or removed when no voltage is applied!
Disconnecting the controller from the mains
Make a safety connection between the controller and mains only via a contactor at the
input side.