Electrical installation – Lenze EMB934x User Manual

Page 125

Advertising
background image

Electrical installation

Circuit proposals

Uncontrolled shutdown of the drive system

5

l

125

EDBMB9340 DE/EN/FR 12.0

Parameter setting of the controller

A detailed description concerning parameter setting can be obtained from the
documentation of the controller.

Parameterise a controller in the system as follows:

1. Invert a digital input Ex and link it with the signal DCTRL−CINH (controller inhibit):

Ex = LOW

W controller inhibit is set.

2. Link a digital output Ax with a function block CMPx (comparator) which compares

the value of the DC−bus voltage (MCTRL−DCVOLT) with the reference value
(FCODE472/x).
Recommended switching points EMB9341 and EMB9342:
– Ax = HIGH if DC−bus voltage > mains voltage x

Ö2 + 75 V

– Ax = LOW if DC−bus voltage < mains voltage x

Ö2 + 50 V

– Adapt the hysteresis to your application.
Recommended switching points EMB9343:
– Ax = HIGH if DC−bus voltage > mains voltage x

Ö2 + 100 V

– Ax = LOW if DC−bus voltage < mains voltage x

Ö2 + 50 V

– Adapt the hysteresis to your application.

Behaviour in case of mains failure during the feedback operation

1. The mains fails. The DC−bus voltage increases.

2. Terminal A2 of the regenerative power supply module indicates mains failure

(A2 = LOW):
– All controllers in the system are inhibited via terminal Ex.
– The master control Z4 also inhibits the controllers (terminal 28 = LOW).
The drives are idling to standstill.

3. When the DC−bus voltage reaches the upper comparator threshold (Ax = HIGH), the

feedback operation at the regenerative power supply module will be inhibited
(E1 = HIGH).

4. When the DC−bus voltage has fallen below the lower comparator threshold

(Ax = LOW), the feedback operation is enabled (E1 = LOW).

5. When the mains voltage is applied again (A2 = HIGH), the master control can

deactivate the controller inhibit (terminal 28 = HIGH).