Controlled shutdown of the drive system, Electrical installation, Stop – Lenze EMB934x User Manual

Page 126: 935x

Advertising
background image

Electrical installation

Circuit proposals
Controlled shutdown of the drive system

5

l

126

EDBMB9340 DE/EN/FR 12.0

5.5.2

Controlled shutdown of the drive system

For controlled shutdown of the drive network additional 935X brake choppers have to be
installed in the network.

The same circuit principle can be used if more braking energy than permissible in the
feedback operation is to be dissipated.

(

Stop!

The regenerative power supply module may be destroyed if the feedback
operation of the regenerative power supply module and the brake chopper are
active at the same time.
For this reason, the circuit must be arranged so that the feedback operation
will be inhibited when the DC−bus voltage reaches impermissible values.

PE U V W

PE U V W

L1

L1

L1

L2

L2

L2

L3

L3

L3

+UG -UG

R

B

935x

+UG -UG

R

B

935x

24 V DC

K10

39

Ex

Ex

28

28

Ax

K10

59

39

Ax

59

E1 39 A1 A2 59

934x

Z2.1

Z4

Z2.n

PE

PE

PE

+UG

+UG

+UG

-UG

-UG

-UG

F4

F6

F8

F5

F7

F9

_

+

=

FAIL

L3’ L2’ L1’ L3.2L2.2L1.2

9340vrm009

Fig. 5−14

Circuit proposal − controlled shutdown of the drive system

934X

Regenerative power supply module

Z2.1 ... Z2.n

Controllers in the drive system

935x

Brake chopper with brake resistor

Z4

Higher−level control (PLC, PC)

K10

Signalling relay "DC bus voltage too high"

F4...F9

DC−bus fuses