Electrical installation

Regenerative power supply module EMB9343
Power connections

5

l

116

EDBMB9340 DE/EN/FR 12.0

5.4

Regenerative power supply module EMB9343

5.4.1

Power connections

(

Stop!

Please observe the following operating conditions:

ƒ

Regenerative power supply modules must not be connected in parallel in
the DC bus.

ƒ

The regenerative power supply module has no overload protection which
means:
– Please observe the permissible mains voltage and maximum currents

(

86). Higher voltages or currents destroy the regenerative power supply

module.

– For protecting the regenerative power supply module against overload

during the regenerative feedback we recommend the use of a brake
chopper. Please observe the circuit proposals (

124).

ƒ

Please observe national and local regulations!