Electrical installation

Regenerative power supply modules EMB9341 and EMB9342

Power connections

5

l

109

EDBMB9340 DE/EN/FR 12.0

Fuses and cable cross−sections

)

Note!

For operating the regenerative power supply module, a mains filter
(accessories) is required.

ƒ

Regenerative power supply module EMB9341: mains filter EZN3A0120H012

ƒ

Regenerative power supply module EMB9342: mains filter EZN3A0088H024

Mains filter A

Installation to EN 60204−1

Installation to UL

Mains (U

N

= 400 ... 480 V)

L1, L2, L3

Load

L1’, L2’, L3’

Mains (U

N

= 480 V)

L1, L2, L3

Load

L1’, L2’, L3’

Type

Fuse

Cable

cross−section

Cable

cross−section

Fuse

Cable

cross−section

Cable

cross−section

EZN3A0120H012

gG/gL 16 A

2.5 mm

2

2.5 mm

2

15 A

AWG 12

AWG 12

EZN3A0088H024

gG/gL 32 A

6 mm

2

6 mm

2

30 A

AWG 9 (8)

AWG 9 (8)

Regenerative
power supply
module

Installation to EN 60204−1

Installation to UL

DC bus

+UG, −UG

Mains synchronisation

L1.2, L2.2, L3.2

DC bus

+UG, −UG

Mains synchronisation

L1.2, L2.2, L3.2

Type

Fuse

Cable

cross−section

Fuse

Cable

cross−section

Fuse

Cable

cross−section

Fuse

Cable

cross−section

EMB9341

32 A

4 mm

2

gG/gL 6 A

1.5 mm

2

20 A

AWG 12

5 A

AWG 16

EMB9342

50 A

6 mm

2 1)

gG/gL 6 A

1.5 mm

2

40 A

AWG 9 (8)

1)

5 A

AWG 16

1)

Observe the ampacity of the cable type!

(

Stop!

ƒ

PE must be connected according to EN 61800−5−1!

ƒ

For the installation acc. to UL, only use UL−approved cables, fuses and fuse
holders.
– UL cables: 60/75 °C or 75 °C copper wire only"
– UL fuses: voltage 500 ... 600 V, tripping characteristic CC", J", T" or R"

Connection plan

I

Tip!

If the power supply of the regenerative power supply is not sufficient, a
parallel supply can be installed via the mains input of one or more controllers
(see controller documentation).