Electrical installation

Circuit proposals
Overload protection in case of power peaks

5

l

128

EDBMB9340 DE/EN/FR 12.0

5.5.3

Overload protection in case of power peaks

)

Note!

When the drive system is dimensioned correctly, no power peaks occur which
could overload the regenerative power supply module.

The behaviour of the drive system described in the following refers to the circuit proposal
and the parameter setting in chapter Controlled shutdown of the drive system" (

126).

1. If the regenerative power of the controllers cannot be dissipated completely due to

the power peaks, the DC−bus voltage increases.

2. If the DC−bus voltage reaches the upper comparator threshold (Ax = HIGH), the

feedback operation is inhibited (E1 = HIGH).

3. With brake chopper: The redundant power is converted into heat via the brake

choppers.
Without brake chopper: The controllers switch over to the fault OU" (overvoltage).
The drives coast.

4. If the DC−bus voltage has dropped to below the lower comparator threshold

(Ax = LOW), the feedback operation is enabled (E1 = LOW).