Electrical installation

Regenerative power supply module EMB9343

Power connections

5

l

117

EDBMB9340 DE/EN/FR 12.0

Fuses and cable cross−sections

)

Note!

For operating the regenerative power supply module EMB9343, a mains filter
(accessories) is required.

ƒ

in systems with UL approval: mains filter EZN3A0055H045U

ƒ

in systems without UL approval: mains filter EZN3A0055H045

Mains filter A

Installation to EN 60204−1

Installation to UL

Mains (U

N

= 400 ... 480 V)

L1, L2, L3

Load

L1’, L2’, L3’

Mains (U

N

= 480 V)

L1, L2, L3

Load

L1’, L2’, L3’

Type

Fuse

Cable

cross−section

Cable

cross−section

Fuse

Cable

cross−section

Cable

cross−section

EZN3A0055H045U

gG/gL 63 A

16 mm

2 1)

Prepared cables

50 A

AWG 4

1)

Prepared cables

EZN3A0055H045

Regenerative
power supply
module

Installation to EN 60204−1

Installation to UL

DC bus

+UG, −UG

Mains synchronisation

L1.2, L2.2, L3.2

DC bus

+UG, −UG

Mains synchronisation

L1.2, L2.2, L3.2

Type

Fuse

Cable

cross−section

Fuse

Cable

cross−section

Fuse

Cable

cross−section

Fuse

Cable

cross−section

EMB9343

100 A

25 mm

2 2)

gG/gL 6 A

1.5 mm

2

80 A

AWG 4

2)

5 A

AWG 16

1)

Connection with pin−end connector

2)

Connection with ring cable lug 6 mm

(

Stop!

ƒ

PE must be connected according to EN 61800−5−1!

ƒ

For the installation acc. to UL, only use UL−approved cables, fuses and fuse
holders.
– UL cables: 60/75 °C or 75 °C copper wire only"
– UL fuses: voltage 500 ... 600 V, tripping characteristic CC", J", T" or R"

Connection plan

I

Tip!

If the power supply of the regenerative power supply is not sufficient, a
parallel supply can be installed via the mains input of one or more controllers
(see controller documentation).